The short answer
  • Most sump pump trouble is the float, the water or the lift.
  • Check the float is free to rise and fall, check the pit has filled to the start level, and check the pump passes what is in the pit and the lift is inside its rating.
  • A pump that trips the RCD or breaker, or hums and does not turn, is a stop and call an electrician.
  • Fit a non return valve to stop it cycling, and stand the pump on a solid flat surface clear of settled silt and debris.
  • No pump handles wipes. The only fix is not flushing them.
  • Send it in for a written report if you are not sure.
Sump pump problems

When a sump pump stops working, the cause is nearly always one of three things: the float cannot move, the pump has the wrong water or too much lift for it, or something electrical has gone. Start with the float and the pit, because they cost nothing to check. Anything behind the terminal cover is an electrician's job.

The short answer

  • Float and water. Is the float free to rise and fall, and is there water in the pit to lift it?
  • Right pump. Does the pump pass what is in the pit, and is the lift inside its rating?
  • Electrics. Tripping the RCD or humming is a stop and call, not a reset and try again.

Why won't my sump pump start?

Isolate the pump first, then work through these in order.

  1. Check the power

    Plug, breaker, RCD, isolating switch. If the RCD is what tripped, leave it off and call an electrician rather than resetting it again.

  2. Check the float is free

    Davey says it plainly: if the float switch is not free to rise and fall, correct pump operation may not be possible. The float needs clear space to swing through its full arc without hitting the wall, the pump body, the cable or the pipework. This is the single most common failure point on a submersible job.

  3. Check there is enough water

    The float starts the pump at a set level. On the Davey D15VAGMA it starts at 230 mm above the base, stops at 140 mm, and the minimum water level is 130 mm. If the pit has not filled to the start level, nothing is wrong.

  4. Let it cool

    The Davey vortex pumps have an automatic resetting thermal overload. A pump that has cut out from overheating will restart by itself once it has cooled, so find out why it got hot: a blockage, a dry run or a stalled impeller.

If it hums and does not turn, leave it isolated. A failed capacitor or a seized impeller looks the same from outside.

Why does it run but not pump?

A pump that runs and moves little or no water has a blocked impeller, too much lift, or the wrong water for it.

Blocked or bound up

Davey warns that lint, hair and fibrous material bind around the pump shaft, and that regular cleaning extends pump life. No pump handles wipes, a grinder included. The only way to deal with wipes is to not flush them. Davey's selection guide lists only its cutter and grinder models for stringy materials in suspension.

Worn by sand and grit

Davey says not to pump abrasive materials. Sand and grit in the water accelerate wear and shorten pump life.

Too much lift

The D15VA and D15VAGMA are rated to 7 m and the D40VA to 7.5 m. Measure from the water in the pit to where the pipe ends. A pump working flat out at its maximum head moves very little water, so step up a size if you are close.

A clean water pump in a dirty pit

The D42A/B passes soft solids to 1.9 mm only. A clean water submersible pushed through silt or leaves will block and overheat, and sooner or later it burns out.

Why does it keep turning on and off?

With no non return valve on the discharge, the water in the pipe runs back into the pit every time the pump stops, which makes the pump cycle on and off. Fit one inside the pit but somewhere you can reach it, because it needs cleaning from time to time. A boxed in float can also do it, so check it can swing. Our submersible pump install guide shows where the non return valve and the union go.

Why does it trip the RCD or breaker?

Stop using it

A pump that trips the RCD or breaker has water in the windings, a damaged cable, a failed capacitor or a stalled motor. Never wedge, bypass or hold in an RCD or breaker that keeps tripping. It is tripping for a reason.

Davey says to use a rope to position and retrieve the pump and never the power lead, because lifting by the lead can damage the cable entry seals and let water in. Davey also says never to lift or carry the pump by the power cable, and never to run it dry, because that damages the seal and reduces the life of the pump.

The capacitor, the float switch and the cord entry are repairs, not owner jobs. Unplug it, lift it out on a rope and bring it to us.

Why does my sump smell?

A smell means water and solids are sitting in the pit. A sump pump cannot empty the pit completely, because the float stops it before it runs dry. On the D15VAGMA it stops at 140 mm above the base. Stopping early is deliberate, because the pump is not meant to run dry. Davey gives a minimum water level of 130 mm for the D15VAGMA.

  • Clean the pit out. Davey's D15VA and D15VAGMA have a recirculation port that keeps soft solids agitated so they pump away, but nothing replaces cleaning.
  • If the pit takes raw sewage, a grinder such as the Davey D75GA is the best pump. A vortex pump can be used for black water as long as the solids are soft, but a grinder is better. No pump handles wipes, so the only fix is not flushing them. See our sewage pumps.

Is it the right pump for what is in the pit?

What is in the pit Pump Passes
Grey water, leaves, silt, soft solids Davey D15VA 20 mm
Same, more flow and bigger solids Davey D40VA 35 mm
Settled effluent, second septic chamber, with a built in float Davey D23AB 1 mm
Clean water to a high head Davey D42A/B 1.9 mm
Toilet waste and sewage Davey D75GA grinder Shredded

Pick the pump for your worst case water, not your average water.

Reading the pump curve

Example pump curve: lift on the upright axis, flow along the bottom, a line falling from left to right with the middle of the curve shaded
An example curve, not a real model. The higher the lift, the lower the flow.

Every pump has a curve showing how much water it moves at each lift (head). The higher you ask it to lift the water, the lower the flow you get, and the more flow you ask for, the less lift it can manage. Pick a pump so your job lands in the middle of its curve, not at either end.

Repair it, replace it, or send it in?

Many failed sump pumps are a repair, and we will tell you straight which. Send the pump in and we send back a written report before any work starts, see pump servicing and repairs. Effluent and sewage pumps must be cleaned, bagged and labelled before they come to us, and you need to tell us it is coming. An unbagged effluent pump will be refused. For which part fails and what it sounds like, read our common pump faults.

To avoid the next one, stand the pump on a solid flat surface clear of settled silt and debris (Davey says timber or house bricks will do if there is none), give the float room, fit a union and a non return valve, and set the float so the pump switches off before the water runs out. See every model in sump and dewatering pumps.

Talk to us

Tell us what the pump does, what is going into the pit and what is on the plate, and we will say whether it is a part or a new pump. A photo of the pit helps. A real person picks up.

65 Kenny Street, Waihi, Mon to Fri 8 to 5. 74 Kopu Road, Kopu, Thames, Mon to Fri 8 to 3.

Talk to us

Tell us what you have and what it is doing. That is usually enough for us to tell you what you are up for. A real person picks up.

65 Kenny Street, Waihi, Monday to Friday 8 to 5. 74 Kopu Road, Kopu, Monday to Friday 8 to 3.